Multifunctional Energy Meter AMC96

Description

Acrel AMC100 series AC precision power distribution monitoring device is a measuring device designed specifically for power management of data center servers.
The device is compact in design and can monitor the full electrical parameters, input and output switches and the status of the lightning arrester of A+B two incoming lines and 192 outgoing lines in real time.

 

Advantage

Communication:

4G,LORAWAN,NB,WIFI

Certificat:

CE

Service:

24HOUR

Cloud Platform:

Iot Platform

 

Size

 

Wiring Diagram

 

 

 

Parameters

AC incoming line

Instrument model AMC100-ZA
Measurement parameters Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, Zero-to-ground voltage, leakage current and zero sequence current, total harmonic content (THD), 2-63 harmonics, current and voltage unbalance, ambient temperature and humidity
Bus voltage Rated 220VAC
Measuring range ±20%
Overload Instantaneous voltage 2 times/sec
Current incoming
circuit
Rated Secondary 5A
Range 0~6A
Overload Continuous 1.2 times, instantaneous 10 times/sec
Temperature and
humidity
Temperature Range -40℃~+99℃
Humidity Range 20%~90%
Input frequency AC45~65Hz
Measurement accuracy Incoming line Voltage/current level 0.2, active power/energy level 0.5, reactive power/energy level 1
Temperature ±1℃
Humidity ±5%
Auxiliary power AMC100-ZA: signal to take power (≤15W)
AMC100-ZA-P220: 220V independent power supply
AMC100-ZA-P24: DC 12-24V independent power supply
Environment Temperature Work: -20℃~150℃ Storage: -25℃~70℃
Humidity Relative humidity≤93%
elevation ≤2500m
Switch output 4 channels 3A 250VAC/3A 30VDC
Switch input 8 dry nodes
Communication 1 isolated RS485/Modbus-RTU to the background system
1 RS485/Modbus-RTU to touch screen
1 RS485/Modbus-RTU connection downstream module Optional 1-channel Ethernet communication function
Installation Method DIN35mm rail or bottom plate installation
Protection level IP20
Pollution level 2
Security Insulation The insulation resistance between all terminals and the conductive parts of the shell is not
less than 100MΩ
Withstand voltage A voltage and current signal//B voltage and current signal//switch output//isolated
communication port//between other ports meet AC2kV 1min, switch input and other ports
should meet AC0.5kV 1min, leakage current Should be less than 2mA, no breakdown or
flashover phenomenon.
Electromagnetic
compatibility 
Anti-static interference Level 4
Anti-electric fast
transient burst
Level 3       
Anti-surge interference Level 4 
Resistance to  radio frequency
electromagnetic field  radiation
Level 3 

    

 

  AC outlet  

Instrument model AMC100-FA30 AMC100-FA48
Measurement parameters Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, 2-31 times total current harmonic content
Bus voltage Rated 220VAC
Measuring range ±20%
Overload Instantaneous voltage 2 times/sec
Current outlet
loop
Rated 50mA
Range 0.125~60mA
Overload Continuous 1.2 times, instantaneous 10 times/sec
Input frequency AC45~65Hz
Measure Outlet Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1
Auxiliary power Powered by AMC100-ZA; DC 12-24V powersupply when used alone
Environment
Temperature Work: -15℃~55℃ Storage: -25℃~70℃
Humidity Relative humidity≤93%
elevation ≤2500m
Communication RS485/Modbus-RTU
Installation Method DIN35mm rail or bottom plate installation
Protection level IP20
Pollution level 2
Security Insulation The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ
Withstand voltag The voltage and current signals of circuit A//the voltage and current signals of circuit
B//other ports meet AC2kV for 1min, the leakage current should be less than 2mA, and there is no breakdown or flashover.
Electromagnetic
compatibility            
Anti-static interference Level 4
Resistance to radio frequency
electromagnetic field radiation
Level 3  

Note: The rated input current of the secondary side of the AMC100-FAK module is 50mA, and the default value of the primary side current is 50A.If the current transformer is different, the customer can set the transformation ratio through the touch screen or the host computer according to the actual use.

 

Instrument model AMC100-FAK48 AMC100-FAK48
Measurement parameters Voltage, current, frequency, active power, reactive power, power factor, active
energy, reactive energy, 2-31 times total current harmonic content
Bus voltage Rated 220VAC
Measuring range ±20%
Overload Instantaneous voltage 2 times/sec
Current outlet
loop
Rated 50mA
Range 0.125~60mA
Overload Continuous 1.2 times, instantaneous 10 times/sec
Input frequency AC45~65Hz
Measure Outlet Voltage/current/active power/active energy level 0.5, reactive power/reactive
energy level 1
Auxiliary power Powered by AMC100-ZA; DC 12-24V powersupply when used alone
Environment Temperature Work: -15℃~55℃ Storage: -25℃~70℃
Humidity Relative humidity≤93%
elevation ≤2500m
Communication RS485/Modbus-RTU
Installation Method DIN35mm rail or bottom plate installation
Protection level IP20
Pollution level 2
Security Insulation The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ
Withstand voltage The voltage and current signals of circuit A//the voltage and current signals of circuit B//other ports meet AC2kV for 1min, the leakage current should be less than 2mA, and there is no breakdown or flashover.
Electromagnetic
compatibility
Anti-static
interference
Level 4
Resistance to radio frequency
electromagnetic
field radiation
Level 3

Note: The rated input current of the secondary side of the AMC100-FAK module is 50mA, and the default value of the primary side current is 50A.If the current transformer is different, the customer can set the transformation ratio through the touch screen or the host computer according to the actual use.

 

Active switch module

Instrument model AMC100-KA30      AMC100-KA48
Input frequency 45-65Hz AC45-65Hz
Auxiliary power  Powered by AMC100-ZA, DC 12-24V powersupply when used alone
Environment Temperature Work: -15℃~55℃ Storage: -25℃~70℃
Humidity Relative humidity≤93%
elevation ≤2500m
Switch input 30 wet nodes (AC 220V) 48 wet nodes (AC 220V)
Communication RS485/Modbus-RTU
Installation Method DIN35mm rail or bottom plate installation
Protection level IP20
Pollution level 2
Security Insulation The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ
Withstand voltage A switch value input signal//B switch value input signal//other ports meet
AC2kV 1min between two, the leakage current should be less than 2mA, no
breakdown or flashover phenomenon.
Electromagnetic
compatibility
Anti-static
interference
Level 4
Resistance to radio frequency electromagnetic field radiation Level 3

 

Passive switch module

Instrument model AMC100-KD30 AMC100-KD48
Auxiliary power Powered by AMC100-ZA, DC 12-24V powersupply when used alone
Environment Temperature Work: -15℃~55℃ Storage: -25℃~70℃
Humidity Relative humidity≤93%
elevation ≤2500m
Switch input 30-way trunk node 48-way trunk node
Communication RS485/Modbus-RTU
Installation Method DIN35mm rail or bottom plate installation
Protection level IP20
Pollution level 2
Security Insulation The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ
Withstand voltage A switch value input signal//B switch value input signal//other ports meet AC2kV 1min between two, the leakage current should be less than 2mA, no breakdown or flashover phenomenon.
Electromagnetic
compatibility
Anti-static interference Level 4
Resistance to radio frequency electromagnetic field radiation Level 3

 

Temperature measurement module

Instrument model AMC100-FT30 AMC100-FT48
Number of measuring channels 30 channels 48 channels
Auxiliary power Powered by AMC100-ZA, DC 12-24V powersupply when used alone
Function Temperature Range -20℃~150℃
Communication RS485/Modbus-RTU
Installation Method DIN35mm rail or bottom plate installation
Protection level IP20
Pollution level 2
Environment Temperature/humidit
y/elevation
Working temperature: -20℃~60℃
Storage temperature: -25℃~70℃
Relative humidity: ≤93%
Altitude: ≤2500m
Security Insulation The insulation resistance between all terminals and the conductive parts of the shell is not less than 100MΩ
Withstand
voltage
AC2kV 1min between auxiliary power supply and temperature measurement, leakage current should be less than 2mA, no breakdown or flashover phenomenon
Electromagnetic
compatibility
Anti-static
interference
Level 4
Resistance to
radio frequency
electromagnetic
field radiation
Level 3

 